name: heat-exchanger-design description: Specialized skill for heat exchanger sizing, rating, and optimization per TEMA standards including shell-and-tube, plate, and air-cooled configurations allowed-tools:
- Read
- Write
- Glob
- Grep
- Bash
metadata:
specialization: mechanical-engineering
domain: science
category: thermal-fluid-analysis
priority: high
phase: 6
tools-libraries:
- HTRI Xchanger Suite
- Aspen Exchanger Design and Rating
Heat Exchanger Design Skill
Purpose
The Heat Exchanger Design skill provides comprehensive capabilities for sizing, rating, and optimizing heat exchangers according to TEMA standards, enabling systematic thermal-hydraulic design of shell-and-tube, plate, and air-cooled heat exchanger configurations.
Capabilities
- Shell-and-tube heat exchanger design and rating
- Plate heat exchanger sizing
- Air-cooled heat exchanger configuration
- LMTD and effectiveness-NTU methods
- Fouling factor consideration
- Pressure drop calculations
- HTRI Xchanger Suite integration
- Thermal-hydraulic optimization
Usage Guidelines
Design Methods
LMTD Method
-
Log Mean Temperature Difference
LMTD = (ΔT1 - ΔT2) / ln(ΔT1/ΔT2) Q = U × A × F × LMTD Where: F = Correction factor for non-counterflow U = Overall heat transfer coefficient A = Heat transfer area -
LMTD Correction Factors
- One shell pass, 2/4/6 tube passes
- Two shell passes, 4/8 tube passes
- Crossflow configurations
Effectiveness-NTU Method
-
Effectiveness Definition
ε = Q_actual / Q_max Q_max = Cmin × (Th,in - Tc,in) -
NTU Calculation
NTU = UA / Cmin Cr = Cmin / Cmax -
Effectiveness Relations
- Counterflow: ε = (1-exp(-NTU(1-Cr)))/(1-Cr×exp(-NTU(1-Cr)))
- Parallel flow: ε = (1-exp(-NTU(1+Cr)))/(1+Cr)
- Shell-and-tube: Complex correlations by TEMA type
Shell-and-Tube Design
-
TEMA Designations
Front End Shell Rear End A - Channel E - One-pass L - Fixed tubesheet B - Bonnet F - Two-pass M - Fixed tubesheet N - Channel J - Divided flow N - Fixed tubesheet - X - Crossflow P - Outside packed - - S - Floating head - - U - U-tube -
Tube Layout
- Triangular pitch (30°): Maximum tubes, poor cleaning
- Square pitch (90°): Mechanical cleaning possible
- Rotated square (45°): Higher turbulence
-
Baffle Design
- Segmental: 20-45% cut
- Double segmental: Reduced pressure drop
- No-tubes-in-window: Vibration mitigation
Plate Heat Exchanger
-
Plate Selection
- Chevron angle (25-65°): Trade-off h vs ΔP
- Plate spacing: 2-5 mm typical
- Pass arrangement: U or Z configuration
-
Design Considerations
- Maximum pressure: 25-30 bar typical
- Maximum temperature: 150-200°C (gaskets)
- Fouling service: Not ideal
Air-Cooled Heat Exchanger
-
Configuration
- Forced draft: Fan below bundle
- Induced draft: Fan above bundle
- Natural draft: No fan (limited duty)
-
Design Parameters
- Face velocity: 2.5-3.5 m/s
- Tube rows: 3-6 typical
- Fin density: 275-435 fins/m
Fouling Considerations
| Service | Fouling Factor (m²K/kW) |
|---|---|
| Cooling water | 0.2-0.35 |
| River water | 0.35-0.5 |
| Fuel oil | 0.5-0.9 |
| Heavy hydrocarbons | 0.35-0.7 |
| Light hydrocarbons | 0.1-0.2 |
| Steam (clean) | 0.05-0.1 |
Process Integration
- ME-012: Heat Exchanger Design and Rating
- ME-011: Thermal Management Design
Input Schema
{
"design_type": "sizing|rating",
"exchanger_type": "shell_tube|plate|air_cooled",
"hot_fluid": {
"name": "string",
"flow_rate": "number (kg/s)",
"inlet_temp": "number (C)",
"outlet_temp": "number (C, for sizing)"
},
"cold_fluid": {
"name": "string",
"flow_rate": "number (kg/s)",
"inlet_temp": "number (C)",
"outlet_temp": "number (C, for sizing)"
},
"pressure_constraints": {
"hot_side_max_dp": "number (kPa)",
"cold_side_max_dp": "number (kPa)"
},
"fouling_factors": {
"hot_side": "number (m2K/kW)",
"cold_side": "number (m2K/kW)"
}
}
Output Schema
{
"duty": "number (kW)",
"geometry": {
"type": "string (TEMA designation or plate type)",
"area": "number (m2)",
"shell_diameter": "number (mm)",
"tube_count": "number",
"tube_length": "number (m)"
},
"thermal": {
"LMTD": "number (C)",
"F_factor": "number",
"U_clean": "number (W/m2K)",
"U_dirty": "number (W/m2K)"
},
"hydraulic": {
"shell_side_dp": "number (kPa)",
"tube_side_dp": "number (kPa)"
},
"performance": {
"effectiveness": "number",
"NTU": "number"
}
}
Best Practices
- Always include fouling factors appropriate for the service
- Verify pressure drop constraints are met on both sides
- Check for vibration potential in shell-and-tube designs
- Consider maintenance access in configuration selection
- Apply TEMA tolerances for manufacturing variations
- Use conservative correlations for preliminary sizing
Integration Points
- Connects with CFD Analysis for detailed flow distribution
- Feeds into HVAC System Design for system integration
- Supports Thermal Analysis for component-level design
- Integrates with Process Design for plant-level optimization